4.7 Article

An experimental study on the effect of ventilation velocity on burning rate in tunnel fires-heptane pool fire case

Journal

BUILDING AND ENVIRONMENT
Volume 43, Issue 7, Pages 1225-1231

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2007.03.007

Keywords

tunnel fire; ventilation velocity; burning rate; n-heptane pool fire; froude scaling

Ask authors/readers for more resources

The 1/20 reduced-scale experiments using Fronde scaling are conducted to investigate the effect of longitudinal ventilation velocity on the burning rate in tunnel fires. The n-heptane pool fires with heat release rate ranging front 3.71 to 15.6 kW are used in this study. A load cell is used to measure the mass loss rate of burning fuel and the temperature distributions are measured by K-type thermocouples in order to investigate smoke movement. The ventilation velocity in the reduced-scale tunnel is controlled by the wind tunnel through an inverter. The increases in ventilation velocity lead to enhance burning rate of n-heptane fuel. The reason is that the oxygen supply effect prevails rather than the cooling effect as the ventilation velocity increases. As a result, the heat release rates in experiment are larger than constant heat release rates by 4.45-11.3 times in the n-heptane pool fires. Also, it is found that non-dimensional critical ventilation velocity is proportional to one-third power of non-dimensional heat release rate. (C) 2007 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available