4.7 Article

Simulation analysis of a two-rolling piston expander replacing a throttling valve in a refrigeration and heat pump system

Journal

APPLIED THERMAL ENGINEERING
Volume 66, Issue 1-2, Pages 383-394

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2014.01.055

Keywords

Expander; Throttling valve; Refrigeration and heat pump system; Two rolling piston; Low pressure refrigerant

Funding

  1. National Science Fund of China [51076111, 50976075]

Ask authors/readers for more resources

An expander is used to replace a throttling valve in a refrigeration and heat pump system in order to improve the system efficiency by recovering partial expansion work. Owing to the large expansion ratios of low pressure refrigerants, a two rolling piston expander was proposed and designed. The efficiency analysis was developed by analyzing energy losses of the expander in the expansion work process. The simulation results show that the friction losses of the designed expander are about 78.5% of total losses, which influences the efficiency of expander significantly. Then the measures of reducing friction losses are presented. A theoretical expander efficiency of 72.0% is expected to be attained. (C) 2014 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available