Radiometric location of partial discharge sources on energized high-voltage plant

Journal

IEEE TRANSACTIONS ON POWER DELIVERY
Volume 20, Issue 3, Pages 2264-2272

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2004.843397

Keywords

condition monitoring; digital monitoring; impulsive noise; partial discharge; radiometric monitoring

Ask authors/readers for more resources

Partial discharges (PD) generate wideband radio frequency interference and, consequently, can be detected using radio receiving equipment. Due to the advances in ultra-high-speed sampling equipment, it is possible to accurately measure the propagation of the PD wavefront as it passes through a 4 element antenna array. From these measurements, the three-dimensional position of the PD source can be calculated using an iterative algorithm. The locating equipment is suitable for use within the vicinity of energized high-voltage plant and can locate sources up to 15 m from the array. Results are presented showing the location ability of the equipment under laboratory and field conditions. A significant advantage is the ability to detect PD sources in energized plant without the need for outages or electrical connections.