4.5 Review

Abbreviated duration of superheat-and-flush and disinfection of taps for Legionella disinfection:: Lessons learned from failure

Journal

AMERICAN JOURNAL OF INFECTION CONTROL
Volume 33, Issue 10, Pages 606-610

Publisher

MOSBY-ELSEVIER
DOI: 10.1016/j.ajic.2004.12.008

Keywords

-

Ask authors/readers for more resources

One medical center in southern Taiwan faced an outbreak of nosocomial Legionnaires' disease; a total of 81 suspected cases were detected during an 8-month period. Baseline environmental surveillance showed that 80% of the distal sites in intensive care units (ICUs) were positive for Legionella pneumophila Superheat-and-flush was selected for hospital water supply disinfection because it required no special equipment, and it can be initiated expeditiously We conducted 2 episodes of superheat-and-flush based on the published recommendations from the Department of Health, Taiwan US Centers for Disease Control and Prevention; and American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Both flushes failed to control colonization of Legionella in the hospital water supply The rate of distal sites positive for Legionella in wards and ICUs was 14% and 66%, respectively, 10 days after the second flush. The effect of replacement of faucets and showerheads in ICUs appeared to be insignificant in colonization of Legionella. The application of superheat-and-flush for flush duration of 5 minutes was ineffective. Superheat-and-flush may not be economic for a large medical center because it could be costly and labor intensive.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available