4.5 Article

Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor

Publisher

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2015.06.021

Keywords

R152a; R134a; F-gas; Hermetic compressor; Internal heat exchanger; GWP

Funding

  1. Jaume I University of Spain [P1.B2013-10]

Ask authors/readers for more resources

The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming Potential (GWP(100)) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a. The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional drop-in process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a. (C) 2015 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available