4.8 Article

Repetitive. based controller for a UPS inverter to compensate unbalance and harmonic distortion

Journal

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Volume 54, Issue 1, Pages 504-510

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2006.888803

Keywords

delay lines; harmonic distortion; repetitive control; uninterruptible power systems

Ask authors/readers for more resources

This paper discusses a repetitive-based controller for an uninterruptible power supply (UPS) inverter. It is shown that a bank of resonant filters, used as a refinement term for harmonic compensation in earlier works, is equivalent to a repetitive scheme with a particular structure. The latter is implemented using a simple feedback array with a delay line, thus making the implementation relatively easy. More precisely, the repetitive scheme takes a negative feedback structure plus a feedforward path whenever the odd harmonics are considered for compensation only. The repetitive scheme, equivalent to the bank of resonant filters, acts as a refinement term to reject the harmonic distortion caused by the unbalanced and distorted load current, and thus, allowing the UPS inverter to deliver an almost pure sinusoidal balanced voltage. Experimental results in a 1.5 KVA three-phase inverter are included to show the performance of the proposed controller.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available