4.7 Article

Performance of energy recovery ventilator with various weathers and temperature set-points

Journal

ENERGY AND BUILDINGS
Volume 39, Issue 12, Pages 1202-1210

Publisher

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2006.12.010

Keywords

energy recovery ventilator (ERV); simulation; availability; energy performance

Ask authors/readers for more resources

Based on the generic dynamic building energy simulation environment, EnergyPlus, the simulation model of energy recovery ventilator (ERV) is developed in this paper. With different indoor temperature set-points, the energy performance of ERV along with the availability of ERV is investigated both for Beijing and Shanghai weathers in China in terms of the ratio of heat recovery to energy supply by HVAC devices and ERV. Simulation results show that the seasonal average of the ratio is linear with indoor temperature set-points. The availability of ERV in Shanghai is better than that in Beijing during the winter. In summer, the utilization of ERV is uneconomical if the indoor temperature set-point is higher than 24 degrees C for the Beijing climate. The indoor temperature set-points have the reverse effects to the availability of ERV in the mid-season and to that in the hottest months. Meanwhile, the heating amount recovery in summer and the cooling amount recovery in winter, both of which impair the strong points of the energy recovery, are analyzed quantitatively. (C) 2007 Published by Elsevier B.V.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available