Journal
ENERGIES
Volume 11, Issue 6, Pages -Publisher
MDPI
DOI: 10.3390/en11061544
Keywords
micro-grid inverter; virtual synchronous generator; quasi-synchronization; islanding detection; smooth-switch control strategy
Categories
Funding
- National Natural Science Foundation of China [51407085]
- Postdoctoral Science Foundation of China [2015M571685]
- Priority Academic Program Development of Jiangsu Higher Education Institution
- Jiangsu University Senior Talents Special Project [13JDG111]
Ask authors/readers for more resources
In allusion to the virtual synchronous generator (VSG)-based voltage source inverters in micro-grids, an integrated control method combining a quasi-synchronization algorithm and an islanding detection algorithm is proposed to improve the power supply reliability and quality, which can simultaneously meet the operational requirements of both grid-connected mode (GCM) and off-grid mode (OGM), and the smooth switching between them. The quasi-synchronization algorithm of the micro-grid inverter is designed to realize a flexible grid connection. Moreover, for quickly detecting islanding phenomena, a novel islanding detection algorithm based on the VSG's inherent characteristics is put forward. Finally, the validity and availability of the proposed models and control strategies are comprehensively verified by simulation results based on Matlab/Simulink.