4.7 Article

Positive impact of a tower inlet cover on natural draft dry cooling towers under crosswind conditions

Journal

APPLIED THERMAL ENGINEERING
Volume 139, Issue -, Pages 283-294

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2018.04.129

Keywords

Natural draft dry cooling tower; Numerical simulation; Crosswind

Funding

  1. Fundamental Research Funds for the Central Universities [2017QNA07]

Ask authors/readers for more resources

This study proposes a tower inlet cover to improve the performance of the small natural draft dry cooling tower (NDDCT) under crosswind conditions. CFD analyses are performed on a small NDDCT with tower inlet covers of different lengths, and the CFD model is validated against experimental results. The air temperature, air pressure, air flow and heat flux fields are presented, and the thermal performance for each heat exchanger and the NDDCT are obtained using CFD simulations. The CFD simulation results show that the high-pressure zone around the tower side wall, formed by the crosswind, causes the decrease in air flow through the tower and the deterioration in tower performance with a crosswind. The tower inlet cover can improve the tower performance in crosswinds by increasing the air flow of the heat exchangers. Tower inlet covers with lengths of 1.5 m, 3 m and 4.5 m improve the tower heat load by 40-65%, 70-130% and 85-230%, respectively, when the crosswind increases from 4 m/s to 12 m/s.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available