4.2 Article

DEVELOPMENT OF ZL400 MINE COOLING UNIT USING SEMI-HERMETIC SCREW COMPRESSOR AND ITS APPLICATION ON LOCAL AIR CONDITIONING IN UNDERGROUND LONG-WALL FACE

Journal

ARCHIVES OF MINING SCIENCES
Volume 61, Issue 4, Pages 949-966

Publisher

POLSKA AKAD NAUK, POLISH ACAD SCIENCES
DOI: 10.1515/amsc-2016-0063

Keywords

coalmine; heat injuries; cooling unit; long-wall working face; ventilation and cooling

Funding

  1. National Key Technology Research and Development Program of the Ministry of Science and Technology of China [2012BAK04B02]
  2. Major Program of Innovation Foundation of China Coal Technology & Engineering Group [2011ZD001]
  3. National Natural Science Foundation of China [41672343]

Ask authors/readers for more resources

Aiming at heat injuries occurring in the process of deep coal mining in China, a ZL400 mine-cooling unit employing semi-hermetic screw compressor with a cooling capacity of 400 kW is developed. This paper introduced its operating principle, structural characteristics and technical indexes. By using the self-built testing platform, some parameters for indication of its operation conditions were tested on the ground. The results show that the aforementioned cooling unit is stable in operation: cooling capacity of the unit was 420 kW underground-test conditions, while its COP (coefficient of performance) reached 3.4. To address the issue of heat injuries existing in No. 16305 U-shaped long-wall ventilation face of Dining No. 3 coal mine, a local air conditioning system was developed with ZL400 cooling unit as the system's core. The paper presented an analysis of characteristics of the air current flowing in the air-mixing and cooling mode of ZL400 cooling unit used in air intake way. Through i-d patterns we described the process of the airflow treatment, such as cooling, mixing and heating, etc. The cooling system decreased dry bulb temperature on working face by 3 degrees C on average and 3.8 degrees C at most, while lowered the web bulb temperature by 3.6 degrees C on average and 4.8 degrees C at most. At the same time, it reduced relative humidity by 5% on average and 8.6% at most. The field application of the ZL400 cooling unit had gain certain effects in air conditioning and provided support for the solution of mine heat injuries in China in terms of technology and equipment.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.2
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available