Investigation on thermal design of a rack with the pulsating heat pipe for cooling CPUs

Journal

APPLIED THERMAL ENGINEERING
Volume 110, Issue -, Pages 390-398

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.08.187

Keywords

Numerical simulation; Cooling; Rack; Pulsating heat pipe; Data center

Funding

  1. National Natural Science Foundation of China [51376019]

Ask authors/readers for more resources

A rack cooling system with the pulsating heat pipe and inner duct in data center is suggested and the heat transfer performance is numerically investigated in this paper. The inner structure of the rack is designed and analyzed. The simplified thermal conductivity model of the pulsating heat pipe is introduced in numerical simulation. The temperature of CPUs (Central Processing Units) is evaluated based on the rack electricity power, the working state of the pulsating heat pipe, the temperature of the cooling air and the wind pressure of the rack fans. The results show that the CPUs temperature increases with the rack heating power. The start-up of the pulsating heat pipe (PHP) leads to the temperature of CPUs decrease and the distribution of temperature of CPUs uniformly. The temperature of CPUs decreases with the decrease of the temperature of the cooling air or the increase of wind pressure. The temperature field of the inner air is improved and some hot spots are removed by installing an inner duct in the rack. The temperature of CPUs is no more than 60 degrees C in the rack cooling system with load 1380 W. (C) 2016 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available