4.8 Article

Modeling of HVAC operational faults in building performance simulation

Journal

APPLIED ENERGY
Volume 202, Issue -, Pages 178-188

Publisher

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2017.05.153

Keywords

Operational fault; HVAC system; EnergyPlus; Modeling and simulation; Energy performance; Thermal comfort

Funding

  1. Assistant Secretary for Energy Efficiency and Renewable Energy of the U.S. DOE [DE-AC02-05CH11231]

Ask authors/readers for more resources

Operational faults are common in the heating, ventilating, and air conditioning (HVAC) systems of existing buildings, leading to a decrease in energy efficiency and occupant comfort. Various fault detection and diagnostic methods have been developed to identify and analyze HVAC operational faults at the component or subsystem level. However, current methods lack a holistic approach to predicting the overall impacts of faults at the building level an approach that adequately addresses the coupling between various operational components, the synchronized effect between simultaneous faults, and the dynamic nature of fault severity. This study introduces the novel development of a fault-modeling feature in EnergyPlus which fills in the knowledge gap left by previous studies. This paper presents the design and implementation of the new feature in EnergyPlus and discusses in detail the fault-modeling challenges faced. The new fault-modeling feature enables EnergyPlus to quantify the impacts of faults on building energy use and occupant comfort, thus supporting the decision making of timely fault corrections. Including actual building operational faults in energy models also improves the accuracy of the baseline model, which is critical in the measurement and verification of retrofit or commissioning projects. As an example, EnergyPlus version 8.6 was used to investigate the impacts of a number of typical operational faults in an office building across several U.S. climate zones. The results demonstrate that the faults have significant impacts on building energy performance as well as on occupant thermal comfort. Finally, the paper introduces future development plans for EnergyPlus fault-modeling capability. (C) 2017 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available