4.6 Article

Harmony search algorithm and combined index-based optimal reallocation of generators in a deregulated power system

Journal

NEURAL COMPUTING & APPLICATIONS
Volume 31, Issue 6, Pages 1949-1957

Publisher

SPRINGER LONDON LTD
DOI: 10.1007/s00521-017-3177-3

Keywords

Optimal reallocation; Static VAR compensator; Harmony search algorithm; Voltage stability

Ask authors/readers for more resources

It is compulsory for the electrical industry to make effective utilization of the available resources and provide a stable and reliable supply to the consumers. Optimal reallocation of generators and implementation of FACTS devices have been found to be very effective in this regard. In this paper, a combinatory strategy of optimal tuning of generators using harmony search algorithm in the presence of static VAR compensator has been proposed. The static VAR compensator has been placed on the basis of a combined index that comprises of V-i/V-o index and L-index. A multi-objective function comprising of voltage deviations, active power generation costs and line losses has been considered for proper tuning of the generators. The results obtained are compared with the genetic algorithm. The proposed method has been tested and implemented on an IEEE 30 bus system for normal loading and for severe system conditions due to line outage.