3.8 Article

Research on commutation failure of Jinsu DC transmission project caused by a complex AC fault

Journal

JOURNAL OF ENGINEERING-JOE
Volume -, Issue 16, Pages 775-778

Publisher

INST ENGINEERING TECHNOLOGY-IET
DOI: 10.1049/joe.2018.8374

Keywords

commutation; power transmission faults; HVDC power transmission; power transmission control; power grids; digital simulation; failure analysis; HVDC power convertors; HVDC project; commutation failure event; Jinsu DC transmission project; complex AC failure; complex AC fault; receiving-end power grid

Ask authors/readers for more resources

Commutation failure is an important factor on safe and stable operation of the receiving-end power grid for high voltage direct current (HVDC) project. A commutation failure event in Jinsu DC transmission project caused by a complex AC failure was taken as background, process of fault and action sequences of protection was introduced, and the reason of the commutation failure and protection action was analysed from principle. Real-time digital simulation (RTDS) was connected to the true-type device of ultra-high voltage direct current (UHVDC) control and protection to form a closed-loop simulation platform. The commutation failure event was inversed, and the simulation result was compared with the actual recorded wave. The results show that abnormal AC voltage leads to the commutation failure.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

3.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available