3.8 Article

Simulation and analysis of ±1100kV UHVDC transmission system with hierarchical connection mode based on PSCAD/EMTDC

Journal

JOURNAL OF ENGINEERING-JOE
Volume -, Issue 16, Pages 1687-1691

Publisher

INST ENGINEERING TECHNOLOGY-IET
DOI: 10.1049/joe.2018.8837

Keywords

commutation; earthing; HVDC power transmission; power transmission faults; power system interconnection; invertors; power transmission protection; hierarchical connection mode; ultra-high-voltage direct current transmission system; control logic; voltage balance control module; low-end converter stations; electromagnetic transient equivalent model; simulation software electromagnetic transient design; EMTDC; PSCAD; simulation analysis; DC control system; power systems computer-aided design; PSCAD-EMTDC environment; UHVDC transmission system; Zhundong-Huadong UHVDC transmission project; voltage 1100; 0 kV

Funding

  1. National Key Research and Development Program [2016YFB0900801]
  2. National Natural Science Foundation of China [51577150]

Ask authors/readers for more resources

This study first introduces the structure and principle of the control system of ultra-high-voltage direct current (UHVDC) transmission system with hierarchical connection mode, mainly including the whole control logic, the voltage balance control module of high-end and low-end converter stations and the commutation failure prediction function. On this basis, this study sets up an electromagnetic transient equivalent model of UHV AC/DC interconnected system with hierarchical connection mode by simulation software electromagnetic transient design and control/power systems computer-aided design (EMTDC/PSCAD) based on Zhundong-Huadong +/- 1100kV UHVDC transmission project. The simulation analysis was first carried out in steady-state operation. Comparing the electrical parameters of the model under the condition of bipolar total voltage with the actual project, the model is consistent with actual engineering parameters. Next, the simulation was undertaken when single-phase grounding fault occurs on AC bus of rectifier side and inverter side. Finally, simulation waveforms and corresponding conclusion are summarised in this study. The results indicate that the DC control system established with hierarchical connection mode under the PSCAD/EMTDC environment has good adjustment effect and can provide a good reference for practise.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

3.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available