4.6 Article

Search Coil Based Online Diagnostics of Transformer Internal Faults

Journal

IEEE TRANSACTIONS ON POWER DELIVERY
Volume 32, Issue 6, Pages 2520-2529

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2017.2682083

Keywords

Interturn fault; search coil; transformer internal faults; winding radial displacement

Ask authors/readers for more resources

An online approach based on application of search coil for transformer winding fault detection is presented in this paper. Earlier attempts report use of search coil for the detection of transformer interturn fault. This paper extends application of search coil for detection of winding displacement in addition to interturn fault identification. Experimental results based on specially designed 10-kVA transformer are presented to analyze search coil voltages during healthy and faulty conditions. The algorithm detects phase (U, V, W), side (LV, HV), and precise location of the fault. Discrimination between interturn fault and winding radial displacement is also achieved by search coil voltage analysis. The results are experimentally verified based on impedance analyzer plots. Experimental analysis indicates that the proposed method is independent of load on the transformer, vector group, nature of winding, balanced or unbalanced source voltage, source voltage harmonics, inrush, and overexcitation conditions.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available