Journal
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Volume 64, Issue 9, Pages 7277-7279Publisher
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2017.2696489
Keywords
Distributed generation (DG); inverter; islanding detection; Sandia frequency shift (SFS)
Categories
Funding
- Enedis Industrial Chair on Smart Grids research program
Ask authors/readers for more resources
We read with interest an article by Zeineldin and Salama, published in the IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS (vol. 58, no. 1, pp. 139-146, Jan. 2011) and tried to reproduce the results of this article for the needs of our own research. Unfortunately, we were led to think that the load model equations used by the authors contained an inconspicuous but significant mathematical error, leading to erroneous results and conclusion. This letter brings corrections to some figures and their analysis as well as the paper conclusion. The new results show that the load's frequency dependence has actually no significant impact on the NDZ of the SFS method.