4.7 Article

Enhanced Commutation Failure Predictive Detection Method and Control Strategy in Multi-Infeed LCC-HVDC Systems Considering Voltage Harmonics

Journal

IEEE TRANSACTIONS ON POWER SYSTEMS
Volume 36, Issue 1, Pages 81-96

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2020.3008726

Keywords

Harmonic analysis; Inverters; Power system harmonics; Voltage control; Firing; Delays; HVDC transmission; Commutation failure control; commutation failure detection; extinction angle; multi-infeed LCC-HVDC systems; voltage harmonics

Funding

  1. National Natural Science Foundation of China [51907067]

Ask authors/readers for more resources

This paper investigates the issue of commutation failure caused by voltage harmonics in multi-infeed LCC-HVDC systems, proposing an enhanced predictive detection method and control strategy. The enhanced method accurately detects and mitigates CF, ensuring fast response speed for practicality.
Voltage harmonics are very likely to cause commutation failure (CF) in multi-infeed LCC-HVDC systems. However, this has not been sufficiently considered in earlier CF detection methods and control strategies. In this paper, by incorporating the voltage harmonics into the inverter quasi-steady-state model, an extinction angle predictive algorithm is firstly presented to propose the enhanced CF predictive detection method. Compared to earlier methods, the enhanced method can detect both local and concurrent CFs more accurately. Moreover, the enhanced method is then used as the starting unit of the enhanced CF predictive control strategy to enable its effective activation. To develop the enhanced strategy, a firing angle order predictive algorithm is introduced using the inverter quasi-steady-state model with the voltage harmonics considered. Compared to earlier strategies, the enhanced strategy can mitigate both local and concurrent CFs more effectively. Furthermore, the response speed of the enhanced method and strategy is evaluated by comparing CF characteristics and signal process delay. It is shown that since the timescales of the voltage harmonics induced CFs are longer than signal process delay, the response speed is fast enough to ensure their practicality. Finally, simulation results based on a dual-infeed LCC-HVDC system validate the enhanced method and strategy.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available