Heat transfer and friction factor correlations for a solar air heater duct roughened artificially with broken arc ribs

Journal

EXPERIMENTAL THERMAL AND FLUID SCIENCE
Volume 80, Issue -, Pages 77-89

Publisher

ELSEVIER SCIENCE INC
DOI: 10.1016/j.expthermflusci.2016.07.022

Keywords

Solar air heater; Friction factor; Rib roughness; Artificial roughness; Nusselt number

Funding

  1. University Grants Commission (UGC)- India [41-987/2012 (SR)]

Ask authors/readers for more resources

In present experimental investigation, solar air heater duct with aspect ratio 12 roughened with broken arc rib has been investigated. The broken arc was formed by creating symmetrical gap in continuous arc. To investigate the influence of roughness parameters of broken arc rib on Nusselt number as well as on friction factor, thirty-seven broken arc rib roughened plates having relative roughness pitch (Pie), relative gap width (g/e), relative gap position (d/w), relative roughness height (e/D-h) and arc angle (alpha) varying from 4 to 12, 0.5 to 2.5, 0.2 to 0.8, 0.022 to 0.043 and 15 degrees to 75 degrees respectively, have been investigated for Reynolds number range of 2000-16,000. Keeping similar flow conditions, results of broken arc rib roughened duct have been compared with smooth and continuous arc rib roughened ducts. The maximum increase in Nusselt number and friction factor over that of continuous arc rib roughened duct was 1.19 and 1.14 times respectively. The corresponding values over that of smooth duct were 2.63 and 2.44 times respectively. Experimental results of heat transfer and friction in flow have also been correlated in terms of flow and roughness geometry parameters. (C) 2016 Published by Elsevier Inc.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available