Time-averaged ventilation for optimized control of variable-air-volume systems

Journal

ENERGY AND BUILDINGS
Volume 139, Issue -, Pages 465-475

Publisher

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2016.11.059

Keywords

Air conditioning; Air distribution; VAV system; Control algorithms; Minimum airflow setpoints; Ventilation

Funding

  1. California Energy Commission (CEC) [PIR-12-026]
  2. Center for the Built Environment (CBE)

Ask authors/readers for more resources

Typical variable air volume (VAV) terminals spend the majority of time at their minimum airflow set points. These are often higher than the minimum ventilation requirements defined by code, resulting in excess energy use and a risk of over-cooling the spaces. We developed and tested a time-averaged ventilation (TAV) control strategy in an institutional building on the UC Berkeley campus to address this issue. Whenever a zone does not require cooling, TAV alternates the VAV damper between partially open and fully closed so that the average airflow matches a predefined ventilation setpoint. Compared to the existing, base case scenario using single-max VAV logic, this strategy reduced the mean zone airflow fraction from 0.44 to 0.27 during the intervention period. The corresponding reductions in average heating, cooling, and fan power were 41%, 23%, and 15% respectively. In addition to being programmed directly in a native control system, TAV may be applied via sMAP as a low-cost retrofit strategy in any building that has a BACnet network and direct digital control (DDC) to each VAV terminal. (C) 2016 Elsevier B.V. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available