Journal
2022 36TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2022)
Volume -, Issue -, Pages 529-534Publisher
IEEE
Keywords
electromagnetic transients; lightning overvoltages; overhead hybrid lines
Categories
Funding
- CAPES Foundation (Higher Education Personnel Improvement Coordination) [88882.179937/2018-01]
Ask authors/readers for more resources
This paper analyzes the overvoltages caused by direct strokes to a hybrid overhead line and discusses their dependence on parameters such as stroke current front time, soil resistivity, and grounding system impedance. It focuses on the voltages on the medium-voltage circuit. A 1:20 scale model has been created, and the measured voltages align well with the calculated values.
This paper analyzes the overvoltages associated with direct strokes to a hybrid overhead line (138 kV and 13.8 kV circuits sharing the same structures). The voltages are calculated using the EMTP-RV, and their dependence on parameters such as the stroke current front time, soil resistivity, and impedance of the grounding system is discussed. Emphasis is given to the voltages on the medium-voltage circuit. A 1:20 scale model of a hybrid line has been implemented, and a good agreement has been found between measured and calculated voltages.
Authors
I am an author on this paper
Click your name to claim this paper and add it to your profile.
Reviews
Recommended
No Data Available