4.7 Article

Experimental study on heating performance of air source heat pump fresh air unit with fresh air and return air mixing in severe cold regions

Journal

ENERGY AND BUILDINGS
Volume 283, Issue -, Pages -

Publisher

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2023.112839

Keywords

Fresh air unit; Fresh air and return air mixing; Air source heat pump; Severe cold regions; COP

Ask authors/readers for more resources

In order to ensure indoor air quality in severe cold regions, this study proposes an air source heat pump fresh air unit that mixes fresh air and return air. The mixing process is carried out in a mixing box, increasing the inlet air temperature of the condenser and ensuring energy-saving and stable operation. Experimental results show that the unit can operate continuously and stably with a fresh air volume of 700 m3/h and a supply air temperature of 24.0 degrees C. The heat pump COP reaches 4.29 at an outdoor temperature of 4.9 degrees C and 2.46 at -20.9 degrees C.
In order to ensure the indoor air quality of the building, in view of the problem of fresh air heating in severe cold regions, this paper proposes an air source heat pump fresh air unit with fresh air and return air mixing. The mixing process of the fresh air and return air is realized in the mixing box, which increases the inlet air temperature of the condenser, creates a suitable condensation pressure, and ensures the energy-saving and stable operation of the unit. In order to explore the operation effect, heating performance and energy saving of the unit, an experimental bench was built in Harbin for laboratory heating. The experimental results showed that when the return air volume was 1400 m3/h, the fresh air unit could operate continuously and stably under the conditions of ensuring the fresh air volume of 700 m3/h and the supply air temperature of 24.0 degrees C. When the outdoor temperature was 4.9 degrees C, the heat pump COP was 4.29. Even when the outdoor temperature dropped to -20.9 degrees C, the heat pump COP still reached 2.46, while the COP of the fresh air system combining electric preheating, heat recovery and air source heat pump was only 1.44, and the COP of the fresh air system combining electric preheating, heat recovery and electric heat was only 1.21. In addition, the heat pump COP increased with the increase of the return air volume. As the set temperature increased, the heat pump COP increased first and then decreased. (c) 2023 Elsevier B.V. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available