Optimization of minor-LiCl-modified gypsum as an effective indoor moisture buffering material for sensitive and long-term humidity control

Journal

BUILDING AND ENVIRONMENT
Volume 229, Issue -, Pages -

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2022.109962

Keywords

Indoor humidity; Moisture buffering; Latent load; Energy saving; Gypsum

Ask authors/readers for more resources

This study investigates the effects of minor LiCl addition on the fundamental properties, hygroscopic performance, and moisture buffering ability of gypsum in daily and weekly humidity fluctuations. Results showed that minor addition of LiCl (1%-8%) significantly improves the gypsum board's properties and hygroscopic performance. The LiCl-modified composites can absorb and desorb moisture repeatedly without hysteresis. Modeling analysis demonstrates that these composites effectively control indoor humidity and achieve energy-saving effects. Based on the results, a LiCl-mixing-ratio of around 4% is proposed as the optimum, providing remarkable moisture buffering and energy-saving capabilities.
Porous gypsum materials buffer indoor humidity autonomously by adsorbing/desorbing moisture but are limited by poor adsorption capacity. Adding hydrophilic salt, such as lithium chloride (LiCl), is known to improve the capacity; however, the hydrophilic salt may block moisture desorption when overused, which is detrimental to moisture buffering and materials durability, particularly on humid days. This paper investigates the effects of minor LiCl addition on the fundamental (thermal conductivity, etc.), hygroscopic (adsorption/desorption), and moisture buffering performance of gypsum in daily and weekly humidity fluctuations. Results showed that minor addition of LiCl (1%-8%) substantially improves the gypsum board's fundamental properties and hygroscopic performance but avoids significant microstructure alteration. The improvement is reinforced with increasing LiCl ratio but then leveled off. The minor-LiCl-modified composites absorbed and desorbed moisture repeatedly without hysteresis for daily and weekly humidity fluctuations. The composite's moisture buffering effects on indoor air and the resulting energy-saving potentials were then modeled with study cases set in Shanghai and Paris; the composites effectively controlled indoor humidity, yielding a good energy-saving on dehumidification. Based on the results, a LiCl-mixing-ratio of similar to 4% was proposed to serve as the optimum, under which the composited gypsum presented a remarkable capacity of 0.16 kg/kg and marked energy-saving by lowering indoor latent load from 7.8 W/m(2) to 3.4 W/m(2) and compensating for the investment increase in 1-2 years. These findings emphasize that implementing minor LiCl to porous gypsum materials enables distinct moisture buffering ability for sensitive and long-term humidity control on indoor air.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available