Experimental study of vacuum-based membrane dehumidifier for HVAC system: Parametric analysis and dehumidification performance

Journal

ENERGY CONVERSION AND MANAGEMENT
Volume 270, Issue -, Pages -

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2022.116252

Keywords

Vacuum-based membrane dehumidifier; Dehumidification performance; Parametric analysis

Funding

  1. National Research Foundation of Korea (NRF) - Korea government (MSIT)
  2. [2022R1A2B5B02001975]

Ask authors/readers for more resources

In this study, a prototype of a vacuum-based membrane dehumidifier was developed and its dehumidification characteristics were evaluated. The results showed that the airflow rate and humidity ratio were key parameters for the dehumidification performance, and the dehumidifier exhibited high dehumidification effectiveness and performance coefficient.
Vacuum-based membrane dehumidifiers (VMDs), an emerging air dehumidification technology, use selective membranes to remove moisture from humid air; these dehumidifiers have the potential to save energy and enhance thermodynamic efficiency through decoupled latent and sensible cooling. In this study, a prototype of a vacuum-based membrane dehumidifier at the scale of an air-conditioning system was developed, and its dehumidification characteristics were experimentally evaluated under various test conditions (i.e., air temper-ature, air humidity, air velocity, and pressure on the permeate side). Four indices were selected to examine the dehumidification performance of the system: the humidity ratio difference, moisture removal rate, dehumidi-fication efficacy, and performance coefficient. The results revealed that the humidity ratio difference ranged 3.38-14.76 g/kg, moisture removal rate 0.16-1.09 kg/h, dehumidification effectiveness 35.4 %-82.7 %, and COP 0.16-0.86. In the parametric analysis of the prototype, the airflow rate and humidity ratio are identified as essential parameters for the dehumidification performance. Moreover, the thermodynamic perspective in the Psychrometric chart and transient operation were utilized to evaluate the operational characteristics of the prototype unit. All experimental results showed that the difference in temperature between the inlet and outlet air was less than 1.5 degrees C, and the saturation time is shown to be within 5 min.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available