4.5 Article

Impact of Firefighting Sprays on the Fire Performance of Structural Steel Members

Journal

FIRE TECHNOLOGY
Volume 58, Issue 4, Pages 2405-2440

Publisher

SPRINGER
DOI: 10.1007/s10694-022-01257-8

Keywords

Firefighting; Water monitors; Fire spread; FDS; Abaqus; FDS2FEM; Adiabatic surface temperature

Funding

  1. Academy of Finland [289037]
  2. Finnish Fire Protection Fund (Palosuojelurahasto)
  3. Academy of Finland (AKA) [289037, 289037] Funding Source: Academy of Finland (AKA)

Ask authors/readers for more resources

The feasibility of using coupled CFD and FE simulations to aid firefighting tactics and structural cooling was investigated. Experimental and simulation results showed that spray cooling can reduce temperatures and halt truss deformation.
The feasibility of coupled computational fluid dynamics (CFD) and finite element (FE) simulations to aid the planning of fire intervention tactics and the effectiveness of structural cooling during firefighting were investigated. Water sprays, generated using fire monitors, were characterized using bucket tests and the results were used for calibrating the CFD spray model. The cooling ability of the sprays was measured experimentally by applying them onto a fire exposed steel beam. The experimental results showed that water application produces a sudden drop in steel temperatures and after 10-15 s, no significant further reduction in temperature was observed. The CFD-FE coupling was performed using the adiabatic surface temperature method, extended here to include the cooling by water droplets. The coupled CFD-FE model was validated using the experimental data and applied to simulate the intervention to a developing warehouse fire, showing how an attempt to cool the structure reduces the temperatures but does not stall the fire-spread. In fact, the intervention -induced vapor generation was found to enhance the flow of hot gases and accelerate the fire-spread if the water resources are inadequate. Thermal and stress analyses of the cooled and uncooled truss beams were performed, showing how the spray cooling halted the truss mid-span deformation.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available