4.7 Article

Individually controlled localized chilled beam with background radiant cooling system: Human subject testing

Journal

BUILDING AND ENVIRONMENT
Volume 218, Issue -, Pages -

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2022.109124

Keywords

Localized chilled beam; Micro-environment; Personal control; Human response; Radiant cooling; Air movement

Funding

  1. Business Finland
  2. International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University of Denmark

Ask authors/readers for more resources

This study compares the responses of subjects to individually-controlled localized chilled beam (LCB) and mixing ventilation (MV) systems. The results show that the LCB system has higher acceptability of the work environment, perceived air quality, and thermal sensation. The LCB system also provides a resilient microenvironment even with changes in room temperature.
This study examines the responses of twenty-four subjects to an individually-controlled localized chilled beam (LCB) and compares it to a mixing ventilation (MV) as the reference system. Both LCB and MV also used ceiling cooling (CC) panels for background cooling (forming LCBCC and MVCC systems). The LCB directed the supply air towards the subjects to create a micro-environment around them. Four experimental conditions were established using a combination of two room temperatures (26 degrees C and 28 degrees C) and two primary ventilation rates (10 l/s and 13 l/s). During the 90 min-long experiments, the subjects were asked to assess their perceived air quality, thermal sensation, comfort, air movement acceptability and acceptability of the work environment. The results indicated that the LCBCC was superior to the MVCC with significantly higher acceptability of the work environment, perceived air quality and thermal sensation. Perceived air quality and thermal sensation were rated near the clearly acceptable level for both room temperatures when LCBCC was used. Moreover, thermal sensation votes were close to the neutral level for room temperatures as high as 26 degrees C and 28 degrees C. The microenvironment established by the LCB was found to be resilient to changes in room temperature. With the MVCC, the thermal environment was rated as slightly warm. No major potential risk of draught among the subjects was reported when using the LCBCC. The findings of this study contribute to the development of hightemperature cooling systems in general, and localized ventilation systems in particular.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available