Using Co-simulation between EnergyPlus and CONTAM to evaluate recirculation-based, demand-controlled ventilation strategies in an office building

Journal

BUILDING AND ENVIRONMENT
Volume 211, Issue -, Pages -

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2021.108737

Keywords

Co-simulation; EnergyPlus; CONTAM; Recirculation of return air; Energy use; IAQ

Funding

  1. Research Council of Norway
  2. Research Centre on Zero Emission Neighborhoods in Smart Cities (FME ZEN) [257660]

Ask authors/readers for more resources

This study developed a coupled simulation model for building energy, airflow, and contaminant transport, and evaluated different strategies for controlling supply air delivery and return air recirculation rates in an office building. The results showed that demand-controlled ventilation strategies and the use of return air recirculation can reduce energy use and improve indoor air quality.
A coupled energy, airflow, and contaminant transport building model was developed using co-simulation between EnergyPlus and CONTAM. The model was used to analyze different strategies to control supply air delivery and return air recirculation rates including the use of demand-controlled ventilation (DCV) strategies. Strategies were evaluated for their effects on indoor pollutant concentrations and energy use of an office building in Trondheim, Norway. Typically, office buildings in Norway employ 100% outdoor air ventilation systems. Measurements in the office building served as the basis to develop the coupled model. The same building was also simulated with the outdoor conditions of Beijing. The results showed that all the simulated DCV strategies yielded reductions in energy use compared to a baseline, schedule-based strategy. Using recirculation of return air was also an energy efficient measure which increased the otherwise low indoor humidity levels in Trondheim. Using CO2-based DCV may result in increased levels of indoor particulate (PM2.5) from outdoors but using PM2.5 monitoring in the ventilation control strategies reduced indoor concentration of PM2.5 and energy usage. However, the low outdoor PM2.5 levels in Trondheim may not justify its use in this location. The Beijing case revealed that the indoor levels of PM2.5 can be reduced below the World Health Organization requirement of annual average of 10 mu g/m(3) using PM2.5 control. Co-simulation results revealed that it is possible to both reduce energy use and improve IAQ by controlling the outdoor air fraction based on multiple pollutants while also considering local outdoor environments.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available