4.7 Article

Multiterminal DC Fault Identification for MMC-HVDC Systems Based on Modal Analysis-A Localized Protection Scheme

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/JESTPE.2021.3068800

Keywords

DC fault; fault identification; localized protection; modular multilevel converter (MMC)-high-voltage dc (HVDC)

Funding

  1. Innovation Fund Denmark through the project multiDC [6154-00020B]

Ask authors/readers for more resources

The proposed work focuses on the identification of DC faults in multiterminal MMC-HVDC systems, specifically addressing selectivity issues and fault classification. Modal transformation and sensitivity functions are used to analyze and identify possible fault scenarios in the system.
For the purpose of dc fault identification in multiterminal modular multilevel converter (MMC) high-voltage dc (HVDC) systems, the proposed work addresses the issues of localized protection schemes. The proposed work is focused on selectivity issues, such as differentiating between forward external and internal faults, and the classification of the type of fault contingency, i.e., pole to pole (PTP) or pole to ground (PTG) in the system. The scheme uses an equivalent network of multiterminal MMC-HVDC systems for de fault identification. Modal transformation is used to analyze line-mode and zero-mode voltages across the current-limiting reactor (CLR) for different possible contingencies in the system. A maloperation region has been defined to address the issue of selectivity of internal HIFs and external low-impedance faults (LIFs). The rate of change of de voltage (dU(dc)/dt) is used as the mitigation technique to differentiate a HIF as high as 1000 Omega. Furthermore, a sensitivity function is formulated, which gives the variation of decisive parameters i.e., line-mode voltage and zero-mode voltage with respect to change in fault resistance and value of CLR. PSCAD-/EMTDC-based simulations are used to validate the performance of the proposed scheme. The scheme is validated in terms of detection time, robustness to WGN in measurement, security for ac faults, dc circuit breaker (DCCB) operation, and power reversal (load transients).

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available