4.7 Article

Joint Topology Identification and State Estimation in Unobservable Distribution Grids

Journal

IEEE TRANSACTIONS ON SMART GRID
Volume 12, Issue 6, Pages 5299-5309

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2021.3102179

Keywords

Topology identification; state estimation; compressive sensing; distribution grids; unobservability

Funding

  1. Department of Energy, Office of Energy Efficiency and Renewable Energy (EERE), Solar Energy Technologies Office [DE-EE0008767]

Ask authors/readers for more resources

The paper proposes a compressive sensing framework to jointly estimate system states and network topology, addressing the challenging problem of topology identification. By investigating two reformulations of the original MINLP problems, the efficiency and accuracy of the solutions are improved. Simulation results illustrate the effectiveness and scalability of the proposed approaches in both state estimation and topology identification, even with limited data available.
Many distribution system operations (e.g., state estimation, control, fault detection/localization) rely on the assumption that the underlying topology is accurately defined. In general, topology identification is a challenging problem in distribution systems as these systems are unobservable with a very limited number of available measurements. In this paper, we tackle this problem by designing a compressive sensing framework that jointly estimates the systems states and network topology via an integrated mixed integer nonlinear program (MINLP) formulation. Two reformulations of the original MINLP problems are investigated. Firstly, in order to remove the nonlinearity in the MINLP formulation, a mixed integer linear programming (MILP) problem that employs auxiliary variables is derived. Furthermore, to achieve a faster solution, convex relaxation of the original formulation is derived. Finally, using a Markovian model for topology changes, prior information about system topology is used to improve topology identification particularly when a limited amount of measurements is available. Simulation results on IEEE 37-bus test feeder and IEEE 123-bus test feeder illustrate the efficiency and scalability of the proposed approaches from both state estimation and topology identification point of view (even with 30% of available data).

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available