4.7 Article

An Online Measuring Method for Tangent Delta of Power Cables Based on an Injected Very-Low-Frequency Signal

Journal

IEEE SENSORS JOURNAL
Volume 22, Issue 1, Pages 980-988

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/JSEN.2021.3129845

Keywords

Cable insulation; online; tangent delta; very low frequency signal

Funding

  1. National Natural Science Foundation of China [51821005]

Ask authors/readers for more resources

The deterioration of cable insulation is a recognized problem, and the measurement of tan delta at VLF is effective for detecting cable insulation. However, the traditional offline method requires power outage, so an advanced online method is proposed in this study, which calculates tan delta based on the measurement of artificially injected VLF voltage and VLF leakage current. The developed equipment and method were successfully applied in the China Electric Power Research Institute, and the measuring results matched the actual conditions, confirming its validity.
The deterioration of cable insulation is a widely acknowledged problem, and detection lays the foundation for maintenance and overhaul. The measurement of Tangent delta (tan delta) at very low frequency (VLF) works well on cable insulation detection, nevertheless the conventional method could only be conducted offline, where the power outage is usually required, interrupting the normal operation. To break thus a limitation, an advanced online method is proposed, and tan delta would be calculated based on the measurement of an artificially injected VLF voltage and that of the VLF leakage current through cable insulation. To coordinate with this method, an injecting source, with the comprehensive self-protection and the by-pass channel for power- frequency signals, is developed to safely inject a VLF voltage to the power system, and a monitoring system, with an accuracy better than +/- 0.3 mu A, is established to obtain the injected voltage's and leakage current's waveforms, which would be used to further calculate tan delta with the cross-correlation algorithm. In addition, this method, as well as developed devices, is applied on several cables in China Electric Power Research Institute, and the measuring results keep consistent with the actual conditions, which verifies the validity.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available