Energy and exergy analysis of an absorption system with working pairs LiBr-H2O and Carrol-H2O at applications of cooling and heating

Journal

INTERNATIONAL JOURNAL OF REFRIGERATION
Volume 132, Issue -, Pages 156-171

Publisher

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2021.09.011

Keywords

Numerical modelling; Absorption; Refrigeration; Heat pump; LiBr; Carrol

Funding

  1. China Scholarship Council Studentship
  2. Ministerio de Ciencia e Innovacion, Spain [PID2020-115837RB-I00]
  3. Catalan Governmen
  4. Polytechnical University of Catalonia

Ask authors/readers for more resources

An evaluation of an air-cooled, single effect solar-driven absorption system using LiBr-H2O and Carrol-H2O as working pairs for absorption chiller and heat pump applications shows that the Carrol system has higher performance and lower crystallization risk in both applications compared to the LiBr system.
In this work, an air-cooled, single effect solar-driven absorption system is being evaluated from the point of view of 1st and 2nd thermodynamic principles for two different applications: absorption chiller and heat pump. One of the most widely used working pairs, LiBr-H2O, is applied in this study due to its high performance in the absorption cycle. Their performance is compared with another working pair Carrol-H2O (Carrol contains LiBr and EG-Ethylene glycol- with a mass ratio of 4.5:1). The Carrol solution has the advantage of reducing the crystallization risk at the high concentration solution that enters the absorber. The numerical modelling was implemented on a modular object-oriented simulation platform (NEST platform tool), which allows linking different components, considered objects. In the simulations performed, the heat source temperature in the system is in the range of 70-90 degrees C, and the inlet temperature at evaporator secondary circuit at chiller application is fixed in two values, 9 degrees C and 14 degrees C, and for heat pump application in 0 degrees C and -5 degrees C. Moreover, EG is added to the evaporator at heat pump application to prevent the refrigerant water from freezing below zero. The studied mass concentration range of EG of 10-40%. The result shows the COP of an absorption chiller and heat pump are around 0.7 and 1.6, respectively, and the COP EX values are 0.2-0.6 at chiller application and 0.5-1.5 at heat pump application. When compared with LiBr system, Carrol system has about 6.4% higher COP, about 6.3% higher COPEX , and a decrease of about 19% of cooling capacity. In the heat pump application, the heat source temperature should be lower than 90 degrees C, and EG concentration at evaporator has been chosen as 30% as an optimal value. According to the operation condition, this EG concentration has been determined to avoid freezing in the evaporator in the studied working range. However, too much EG significantly decreases the pressure in the evaporator and increases the viscosity, hence will increase the maintenance of equipment as more vacuum tightness is required.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available