An airside performance of the wavy fin-and-tube heat exchangers having oval tubes

Journal

APPLIED THERMAL ENGINEERING
Volume 190, Issue -, Pages -

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2021.116807

Keywords

Oval tube; Heat exchanger; Wet surface; Wavy fin; Heat transfer coefficient; Pressure drop

Ask authors/readers for more resources

This study investigated the air-side heat transfer and pressure drop characteristics of fin-and-tube heat exchangers with oval or round tubes. Results showed that oval tube samples had better thermal performance under dry conditions, but the reverse was true under wet conditions due to poor condensate drainage from the oval tube. The pressure drops of round tube samples were larger, and under wet conditions, they were larger than under dry conditions. Also, an interesting feature was noticed where the highest j factor was obtained at a two-row configuration.
In this study, the air-side heat transfer and pressure drop characteristics of the fin-and-tube heat exchangers having an oval tube or a round tube were investigated. Notable things of the samples were that the round and the oval tube had the same perimeter, the fins had the same configuration, and the samples had the same tube pitch. Thus, only the tube shapes were different. The tests were conducted both under dry and wet condition. The thermal performance comparison (eta(o)h(o)A(o)/V-o vs. Delta P/L) revealed that a better performance was resulted from the oval tube samples. Under the wet condition, however, the reverse was true. The oval tube samples yielded an inferior thermal performance, probably due to a poor condensate drainage from the oval tube. The pressure drops of the round tube samples were larger than those of the oval tube samples. Furthermore, the pressure drops under wet condition were larger than those under dry condition. The j factor was relatively independent of the fin pitch, whereas the f factor increased as the fin pitch increased. Under wet condition, however, some interesting feature was noticed. The highest j factor was obtained at a two row configuration. A possible explanation was provided considering the condensate drainage behavior.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available