4.7 Article

Virtual storage capability of residential buildings for sustainable smart city via model-based predictive control

Journal

SUSTAINABLE CITIES AND SOCIETY
Volume 64, Issue -, Pages -

Publisher

ELSEVIER
DOI: 10.1016/j.scs.2020.102491

Keywords

Model-based predictive control; Grey-box model; Pre-cooling; Demand shedding; Virtual storage; Sustainable cities

Funding

  1. United States Department of Energy, Energy Efficiency and Renewable Energy Office, Building Technology Office under the grid modernization program
  2. INHA UNIVERSITY Research Grant

Ask authors/readers for more resources

This study evaluated the virtual storage capability of a residential air-conditioning system by utilizing building mass as thermal storage, through model-based predictive control. The results showed that MPC significantly saved energy costs while improving comfort levels.
This paper evaluates the virtual storage capability of a residential air-conditioning (AC) system by utilizing the building mass as a thermal storage to enable sustainable cities through model-based predictive control (MPC). The control-oriented building model was developed with a grey-box model structure based on the experimental data to predict the indoor air temperature. Based on the model, the operation cost-saving potential of the MPC was investigated in a single house with different comfort levels, electricity prices, and prediction horizons. The cost-saving of the MPC was approximately 10.6 % compared to the conventional control. The MPC was expanded to a residential building cluster considering the peak demand charge. In an hourly shedding and load-up scenario, the performances of the MPC and the heuristic prior-based control (PBC) are promising. When shedding was enforced all day, the peak demand saving of the MPC was 36 similar to 38 %, whereas that of the PBC was 25.7 % compared to the baseline. In addition, the monthly electricity bill, including the operation and peak demand cost, was investigated with different demand charge rates and weather conditions. The total saving decreased with a low demand charge rate and hot conditions, and the operation cost saving was compromised with more aggressive demand shedding.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available