4.5 Article

Modelling of an Existing Neutral Temperature District Heating Network: Detailed and Approximate Approaches

Journal

ENERGIES
Volume 14, Issue 2, Pages -

Publisher

MDPI
DOI: 10.3390/en14020379

Keywords

district heating and cooling; heat pumps; waste heat; ground source; energy modelling

Categories

Funding

  1. LIFE Programme of the European Union [LIFE17 CCM/IT/000085]

Ask authors/readers for more resources

This paper models an existing neutral-temperature district heating network in Ospitaletto, Italy, with industrial waste heat and aquifer wells as heat sources. Two models, a detailed one and an approximate one, are used to analyze the network with different levels of information and execution times, suitable for different purposes.
This paper deals with the modelling of an existing neutral-temperature district heating network, meaning that the distribution temperature is close to the ambient temperature, with decentralised heat pumps. The considered case is located in Ospitaletto, Italy. Heat sources are given by industrial waste heat at about 25 degrees C and aquifer wells at about 15 degrees C. Two models are used to analyse the network: a detailed model able to calculate local values of operating parameters and an approximate model focused on energy balances aggregating all users with a lumped demand. Both models include the behaviour of heat pumps, a feature not available in other district heating modelling tools. An entire year of operation is considered, with an hourly time resolution. Load profiles are provided as inputs, while the main outputs consist of energy balances and primary energy consumptions. The corresponding results are compared, showing a reasonable agreement, where the approximate model underestimates the overall electricity consumptions by about 15% with respect to the detailed model. On the other hand, the different information levels and execution times (the detailed model requires about 30 min to solve the considered network for a full year with hourly time steps, while the approximate model is almost immediate) make the two models suitable for different purposes, like the simulation of control solutions for the detailed one and scenario analysis for the other.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available