4.2 Article

Gray-box virtual sensor of the supply air temperature of air handling units

Journal

SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT
Volume 26, Issue 8, Pages 1151-1162

Publisher

TAYLOR & FRANCIS INC
DOI: 10.1080/23744731.2020.1785812

Keywords

-

Funding

  1. Horizontal Postdoctoral Program of Concordia University
  2. Natural Sciences and Engineering Research Council (NSERC)
  3. Natural Resources Canada

Ask authors/readers for more resources

Building automation system uses several networks of sensors for continuous monitoring of building control systems for energy-efficient operation. Physical sensors are costly and need frequent calibration. The accurate measurement of supply air temperature from the air handling units (AHUs) has an important effect on the control of cooling coil, supply air temperature and supply airflow rate delivered to rooms. In the case when such a sensor gives erroneous measurements, a virtual sensor can replace temporarily the faulty sensor, and it can also be used for automated fault detection of HVAC systems. This article proposes two different gray-box (models A and B) for predicting the supply air temperature of air handling units that were developed and tested using the measurements from two buildings. The models require the measurement of three variables (mixed air temperature, cooling coil valve signal, and chilled water inlet temperature). The results of both models are discussed and compared. A sliding window approach for cross-validation of the models was also carried out. The developed gray-box models A and B could be integrated into BAS for virtual measurement, virtual calibration, and fault detection in HVAC systems.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.2
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available