4.6 Article

Improved Inversion Method for Multi-Regional Oil-Immersed Paper Resistivity in Transformer

Journal

IEEE TRANSACTIONS ON POWER DELIVERY
Volume 35, Issue 3, Pages 1467-1475

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2019.2947653

Keywords

Conductivity; Power transformer insulation; Oil insulation; Mathematical model; Aging; Dielectrics; Oil-paper insulation; resistivity; inversion; Newton downhill method

Ask authors/readers for more resources

Oil-paper insulation ageing of transformer has characteristics of spatial locality due to uneven temperature distribution. The transformer is sealed, it is difficult to obtain the local ageing state of oil-paper insulation by sampling directly. Currently, there are no effective detection method to detect the insulation state of local regions. The oil-immersed paper resistivity inversion method can nondestructively assess the local state of oil-paper insulation. However, the current inversion methods still have shortcomings and need to be improved. In this paper, combining the back propagation neural network (BPNN) and Newton downhill method (NDM), an improved inversion method is proposed to optimize the current inversion method, so as to reduce the effect of initial value on it and make calculated results converge better. Finally, a 3D 10 kV transformer model is established to verify the effectiveness of the proposed method. The resistivity calculated by the improved method show that the method can provide initial resistivity values for technicians and improve the convergence and accuracy of current inversion method, which is more suitable for extending to the engineering practice.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available