4.7 Article

Distributionally Robust Unit Commitment in Coordinated Electricity and District Heating Networks

Journal

IEEE TRANSACTIONS ON POWER SYSTEMS
Volume 35, Issue 3, Pages 2155-2166

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2019.2950987

Keywords

Resistance heating; Cogeneration; Optimization; Mathematical model; Programming; Probability distribution; Coordinated electricity and district heating networks; unit commitment; distributionally robust optimization; linear decision rules; simplified affine policies

Funding

  1. National Natural Science Foundation, China [51877071]
  2. Postgraduate Research & Practice Innovation Program of Jiangsu Province, China [SJKY19_0440]
  3. Fundamental Research Funds for the Central Universities, China [2019B67614]

Ask authors/readers for more resources

Coordinated operations of electricity and district heating networks offer a potential for mitigating inherent variability of renewable energy sources (RES) in the ongoing transition to smart grids. This paper proposes a two-stage distributionally robust optimization (DRO) approach to determine the optimal day-ahead unit commitment in coordinated electricity and district heating networks with variable RES power output. The proposed formulation is to minimize the worst-case expected total cost over an ambiguity set comprising a family of probability distributions with given support and moments of RES power output. As such, the proposed DRO approach can overcome the limitations of stochastic programming in its inherent dependence of exact probability distributions along with a huge computational burden, but also becomes less conservative than classical robust optimization. The pertinent DRO model is eventually reformulated as a tractable mixed-integer second-order cone (SOC) programming after employing linear decision rules and the SOC duality. Simplified affine policies are utilized to further improve computational tractability and performance. Finally, case studies are conducted based on Barry Island electricity and district heating networks. The numerical results demonstrate the decision-making superiority of the proposed method as compared with deterministic, stochastic programming, and robust optimization approaches. They also validate the computational improvement of the proposed approach by employing simplified affine policies.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available