According to the coordination control of a dynamic voltage restorer (DVR) and an inductive fault current limiter (FCL), this paper proposes an efficient low-voltage ride-through (LVRT) scheme for a doubly fed induction generator (DFIG) based wind turbine. The DVR is located to the DFIG's stator circuit for stabilizing the terminal voltage and decreasing the generator current. The inductive FCL is connected to the DFIG's rotor circuit for suppressing the rotor overcurrent and protecting the converter. Theoretical discussions on structure, principle and scale criterion of the combined DVR-FCL are conducted, and simulation analyses of the proposed approach to handle symmetrical and asymmetrical faults are done in MATLAB/Simulink. In this study, the dynamic characteristics of the DFIG during the faults are analyzed from multiple aspects, and a detailed comparison of the proposed approach and the single action of DVR or FCL is carried out. From the simulation results, the effectiveness and superiority of the proposed approach are well demonstrated.