4.5 Article

Thermodynamic performance evaluation of a cascade refrigeration system with mixed refrigerants: R744/R1270, R744/R717 and R744/RE170

Publisher

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2019.07.005

Keywords

Carbon dioxide; Cascade refrigeration; Mixed refrigerants; Simulation; Optimization

Funding

  1. Brazilian Federal Government
  2. Coordenacao de Aperfeicoamento de Pessoal de Nivel Superior Brasil (CAPES) [001, 33003017034P8]

Ask authors/readers for more resources

This work evaluates the thermodynamic performance of three different mixed refrigerants: R744/R1270, R744/R717 and R744/RE170 in a cascade refrigeration system composed of two vapor compression cycles. Mixture composition and condensation temperature of the cascade heat exchanger were used as inputs in a parametric analysis, while outputs considered were: compressor power, refrigerant mass flow rate in both cycles, exergy destruction rate, exergetic efficiency and coefficient of performance. Systems were optimized for COP maximization, considering a fixed cooling rate of 100 kW in the evaporator. After optimization, COP increased from 18% to 32% when compared to the values obtained for pure refrigerants. R744/RE170 mixture showed the best results with a COP of 2.34, increasing exergetic efficiency up to 30% and reducing refrigerant mass flow rate in the range from 6% to 34%, compressor power between 20% to 23% and exergy destruction rate was decreased around 31% to 36%. (C) 2019 Elsevier Ltd and IIR. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available