4.5 Article

Performance analysis of a R407C liquid-to-water heat pump: Effect of a liquid-vapor heat exchanger and domestic hot water production

Journal

INTERNATIONAL JOURNAL OF REFRIGERATION
Volume 101, Issue -, Pages 125-135

Publisher

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2019.02.024

Keywords

Heat pump; Experimental results; Liquid-vapor heat exchanger; Domestic hot water production; Degree of subcooling; Refrigerant charge

Funding

  1. Spanish Ministerio de Economia y Competitividad
  2. FEDER (EU) [ENE2016-79771-R]

Ask authors/readers for more resources

This paper presents an experimental study of a R407C liquid-to-water heat pump for combined space heating (SH) and domestic hot water (DHW) production. The main components of the heat pump are a scroll compressor, a desuperheater for DHW production, two brazed plate heat exchangers (condenser and evaporator) and a thermostatic expansion valve. A liquid-vapor heat exchanger (LVHEx) has been included in order to study its effect on the heat pump performance. Experimental results for typical operating conditions in the heating mode of operation (low and medium temperature applications) are presented and discussed. These operating conditions are combined with simultaneous DHW production at different flow rates and temperature values. Results show that, in general, the COP is higher with simultaneous SH and DHW production than with SH alone. Also, using the LVHEx yields lower heating and compression powers and, in general, slightly lower COP values. (C) 2019 Elsevier Ltd and IIR. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.5
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available