Journal
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID
Volume 101, Issue -, Pages 56-70Publisher
ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2019.02.031
Keywords
Booster compressor; COP; Ejector expansion; Exergy analysis; Optimization; Refrigeration
Categories
Ask authors/readers for more resources
A novel ejector-expansion refrigeration cycle (EERC) is proposed, analyzed and optimized in this paper. Assuming a constant-pressure mixing model for ejector simulation, a detailed and comprehensive thermodynamic analysis, based on the first and second laws, is conducted and the system performance is investigated for six proper refrigerants. The proposed system is then optimized considering the exergy efficiency as the objective function and a comparison is made with the standard EERC and conventional vapor compression refrigeration system at the optimized conditions. The results indicated that, among the six investigated refrigerants, R1234ze is the best one for which the proposed system has 5.7% and 15.5% higher exergy efficiency values than the standard EERC and conventional vapor compression refrigeration cycle, respectively, at condensing temperature of 40 degrees C and evaporation temperature of 5 degrees C. Also, it is concluded that for higher condensing and lower evaporating temperatures the value of performance improvement is higher. (C) 2019 Elsevier Ltd and IIR. All rights reserved.
Authors
I am an author on this paper
Click your name to claim this paper and add it to your profile.
Reviews
Recommended
No Data Available