4.7 Article

Nusselt number and friction factor correlation of solar air heater having twisted-rib roughness on absorber plate

Journal

RENEWABLE ENERGY
Volume 130, Issue -, Pages 687-699

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.renene.2018.06.076

Keywords

Solar air heater; Twisted rib; Regression analysis

Funding

  1. SERB, DST, Govt. of India [SB/EMEQ-314/2013]

Ask authors/readers for more resources

A study is carried out providing integrated roughness over absorber plate of solar air heater to improve its potential for heat transfer augmentation. A number of experiments are conducted with twisted roughness to pursuit test results for heat transfer augmentation along with friction factor phenomena. The experiments stand with a relevant range of flow parameters as Reynolds number from 3500 to 21000, and geometric parameters such as relative roughness pitch from 6 to 10, rib inclination angle domain from 30 to 90 and twist ratio from 3 to 7. Finally, the correlations are developed for the Nusselt number and the friction factor in terms of flow parameter and roughness geometries and compared with experimental results which are reasonable and eventually satisfactory. The enhancement of heat transfer as well as friction factor are obtained and compared with smooth conventional duct for the same flow circumstances. The results are analyzed to pursuit optimum condition of roughness parameters to achieve the best performance. (C) 2018 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available