4.7 Review

Investigation of the thermal behavior of a combined geothermal system for cooling with regards to Algeria's climate

Journal

SUSTAINABLE CITIES AND SOCIETY
Volume 43, Issue -, Pages 121-133

Publisher

ELSEVIER
DOI: 10.1016/j.scs.2018.08.016

Keywords

Earth-air heat exchanger; Underground tank; Soil nature; Seasonal storage model

Ask authors/readers for more resources

In this study an experimental and numerical analysis, of the energy efficiency of a combined geothermal system composed of two series of connected underground tanks coupled with a cooling floor and a PVC earth-air heat exchanger for the pre-conditioning air of a multizone region, located in Oran (Northern Algeria) is presented. Data acquisition system was set up to analyse the energy performance of the cooling system according to the climatic conditions and the nature of the soil in the city of Oran. Experimental results show that this geothermal system provides an increase of 11 degrees C for the climate in this region. Using TRNSYS.16 software, a seasonal storage model has been implemented, where the results have been validated by those obtained in the experiment. Simulations have shown that the energy efficiency of the combined geothermal system is more significant in the arid zone of the south and in the semi-arid zone of the north of the country. A co-simulation between two types of software TRNSYS and FLUENT allowed us to visualize the dynamic thermal behavior of the indoor air and to show the significance of the geothermal air transmitter when it is in use.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available