4.7 Article

Modeling and Control System Design of a Grid Connected VSC Considering the Effect of the Interface Transformer Type

Journal

IEEE TRANSACTIONS ON SMART GRID
Volume 3, Issue 1, Pages 122-134

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2011.2166412

Keywords

Control system design; distributed generation; power electronics; power quality; VSC

Ask authors/readers for more resources

In this paper, modeling and control system design of a three-phase VSC system are investigated. The linear model and the control design are developed in the stationary-frame. The model shows a highly coupled system along alpha and beta coordinates when using a Delta-Y transformer vs. two completely decoupled subsystems in the case of Y-Y transformer. This issue was often overlooked in literature. The developed model includes the phase shift caused by the Delta-Y transformer to address its effect on the steady-state and the dynamic behaviors under balanced and unbalanced distorted three phase conditions. Linear state-space model of the closed-loop system is developed to study the dynamics and stability of the two configurations. Modal analysis shows that the phase shift introduced by the Delta-Y configuration can reduce the ultimate gain of the open loop system by 62% as compared to the system interfaced using Y-Y configuration. The developed linear model has been simulated inMATLAB/SIMULINK and validated using a detailed switching model in PSCAD/EMTDC under balanced and unbalanced three-phase conditions. The proposed control method can provide fast active and reactive power control with a minimum harmonics distortion in the line current.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available