4.6 Article

Analyses of smoke management models in TFT-LCD cleanroom

Journal

BUILDING SIMULATION
Volume 6, Issue 4, Pages 403-413

Publisher

TSINGHUA UNIV PRESS
DOI: 10.1007/s12273-013-0121-z

Keywords

smoke management models; TFT-LCD cleanroom; fire dynamics simulator (FDS); SIMULEX; smoke exhaust system

Funding

  1. National Science Council, Taiwan (NSC) [99-2625-M-261-001-MY3]

Ask authors/readers for more resources

This study evaluated the effectiveness and performance of smoke management models in a TFT-LCD cleanroom. Several smoke management models are discussed in a distinct 3-level cleanroom compartment. The tools used included a fire dynamics simulator (FDS) and SIMULEX. The design fires were 3 MW and 5.4 MW in ultra fast fire, respectively. In life safety, both a downward smoke exhaust system and upward smoke exhaust system, incorporating a decrease of filter fan unit air supply rate, could be used in a cleanroom, according to the simulation results of performance-based design. For occupant evacuation, the SIMULEX results showed a total evacuation time less than smoke layer descending time, which descended to 1.8 m height from floor to smoke layer in all FDS simulations. In view of property protection, insurance companies generally require significantly higher standards of property protection. For 3 MW or more heat release rate, smoke was hardly controlled by any smoke exhaust system in the cleanroom without sprinklers.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available