4.6 Article

Characterization of an effervescent atomization water mist nozzle and its fire suppression tests

Journal

PROCEEDINGS OF THE COMBUSTION INSTITUTE
Volume 33, Issue -, Pages 2573-2579

Publisher

ELSEVIER SCIENCE INC
DOI: 10.1016/j.proci.2010.06.001

Keywords

Effervescent atomization; Two-phase flow; Water mist; Fire suppression

Funding

  1. Natural Science Foundation of China [50774072]
  2. Program for New Century Excellent Talents in University [NECT-07-0794]
  3. State Key Laboratory of Fire Science [HZ2007-KF08]

Ask authors/readers for more resources

A gas-outside-liquid-inside water mist nozzle based on effervescent atomization technology is designed, characterized and tested in this paper. The droplets size distribution, velocity under different operation pressures and gas-liquid-ratios (GLR) are measured with a Phase Doppler Analyser (PDA). The gas flow rate, liquid flow rate of the nozzle with one or seven orifices are also characterized under different operation pressures and GLR conditions, respectively. The results show that all of above parameters are mainly influenced by GLR, i.e., the larger the GLR is, the smaller the droplet size will be, and the liquid mass flow rate is exponentially increased with the increasing of GLR. The test results of fire suppression show that this gas-outside-liquid-inside effervescent atomizer works well for fire extinguishment except the cases where the liquid flow rate is less than about 70 kg/h and the gas pressure is lower than 0.3 MPa. (C) 2010 The Combustion Institute. Published by Elsevier Inc. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available