4.7 Article

Wicking and thermal characteristics of micropillared structures for use in passive heat spreaders

Journal

INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Volume 55, Issue 4, Pages 586-596

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2011.10.053

Keywords

Heat pipe; Thermal spreaders; Wick structure; Evaporation; Micro-pillars

Ask authors/readers for more resources

The thermal and hydrodynamic performance of passive two-phase cooling devices such as heat pipes and vapor chambers is limited by the capabilities of the capillary wick structures employed. The desired characteristics of wick microstructures are high permeability, high wicking capability and large extended meniscus area that sustains thin-film evaporation. Choices of scale and porosity of wick structures lead to trade-offs between the desired characteristics. In the present work, models are developed to predict the capillary pressure, permeability and thin-film evaporation rates of various micropillared geometries. Novel wicking geometries such as conical and pyramidal pillars on a surface are proposed which provide high permeability, good thermal contact with the substrate and large thin-film evaporation rates. A comparison between three different micropillared geometries - cylindrical, conical and pyramidal - is presented and compared to the performance of conventional sintered particle wicks. The employment of micropillared wick structure leads to a 10-fold enhancement in the maximum heat transport capability of the device. The present work also demonstrates a basis for reverse-engineering wick microstructures that can provide superior performance in phase-change cooling devices. (C) 2011 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available