4.7 Article

General characteristics of two-phase flow distribution in a compact heat exchanger

Journal

INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Volume 52, Issue 1-2, Pages 442-450

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2008.05.030

Keywords

Two-phase flow; Maldistribution; Compact heat exchangers

Funding

  1. CEA (Atomic Energy Commissary)
  2. ADEME (Agency for Environment and Energy Control)

Ask authors/readers for more resources

An experimental loop representing a compact plate heat exchanger was built up to study the two-phase distribution in the different header channels. The test section consists of a cylindrical horizontal header and eight rectangular channels in which the liquid and vapour flow rates are evaluated and the flow inside the header can be visualized. Several geometrical and functional parameters to study the two-phase distribution were tested using HFE 7100 at a temperature close to 57 degrees C and a pressure close to 100 kPa. A flow pattern map in the header was built up using the different entry parameters on which a quantitative understanding of the two-phase distribution could be deduced. (c) 2008 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available