Journal
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS
Volume 55, Issue -, Pages 297-304Publisher
ELSEVIER SCI LTD
DOI: 10.1016/j.ijepes.2013.09.017
Keywords
Automatic generation control; Diverse sources power system; Optimal AGC regulator; AC/DC links
Categories
Ask authors/readers for more resources
This paper presents a comprehensive study on dynamic performance of a more realistic power system with diverse sources in each area and interconnected via parallel AC/DC transmission links. The power generation in each area is based on diverse sources such as thermal, hydro and gas. To carry out the investigations, optimal Automatic Generation Control (AGC) regulators are designed and implemented by considering an example of a two area power system for 1% step load disturbance in one of the control areas. In order to assess the improvement in stability of this realistic power system with DC link in parallel with AC tie-line as interconnection, eigenvalue study is also conducted. It has been shown that the transient response of power system subject to a step load disturbance is sluggish/poor in the presence of hydro as one of the diverse source in the power system. But an appreciable improvement in system dynamic performance is achieved by considering parallel AC/DC links as interconnection between areas rather than using AC tie lines only. (C) 2013 Elsevier Ltd. All rights reserved.
Authors
I am an author on this paper
Click your name to claim this paper and add it to your profile.
Reviews
Recommended
No Data Available