Advanced coordination method for overcurrent protection relays using nonstandard tripping characteristics

Journal

IEEE TRANSACTIONS ON POWER DELIVERY
Volume 23, Issue 1, Pages 52-57

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2007.905337

Keywords

optimization method; overcurrent protection; protection coordination; selectivity; tripping characteristic; tripping time

Ask authors/readers for more resources

This paper describes an advanced coordination method for an optimized protection time grading based on a new nonstandard tripping characteristic for overcurrent protection relays. The intention is the highest possible reduction of tripping times for a selective fault clearing in distribution networks protected by overcurrent relays without communication links. The new nonstandard tripping characteristic will be described from its basic idea to its constraints of the optimization problem. The optimization is solved by the method of Lagrange generalized with the Karush-Kuhn-Tucker conditions and is aimed at selective fault tripping with shorter tripping times as standard characteristics and conventional coordination methods. Overcurrent relay coordination becomes a mathematical optimization task. A comparison with the standard characteristics and conventional coordination methods shows a notable advancement regarding their average and maximum tripping times which can be achieved using this new method.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.6
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available